Belimo Part Number: P6300S-141+AKRX24-PI
Torque: 180 in-lb [20Nm]
Valve Size: 3"
Flow Pattern: 2 Way
Flow Characteristic: equal percentage/linear
Power Supply: 24 VAC 20%, 24 VDC 10%
Running Time (motor): --
Running Time (fail-safe): 35 seconds
Technical Data Sheet
> Valve Specifications |
Service | chilled or hot water, 50% glycol max (closed loop/steam not allowed) |
Flow characteristic | equal percentage / linear |
Controllable flow range | 90 degrees rotation |
Size | 2, 3, 4, 5, 6 |
Type of end fitting | pattern to mate with ANSI 125 flange |
Body pressure rating | according to ANSI 125, standard class B |
Media temp. range | 36deg.F to 250deg.F [2deg.C to 120deg.C] |
Conductivity | Min. 20uS/cm (no fully desalinated systems) |
Leakage | 0% |
Differential pressure range(delte-P) | 5 to 50 psid |
Inlet length required in front of valve | 5x DN |
Power supply for the flow sensor | sensor is powered by the actuator |
Materials |
Body | cast iron - GG25 and ductile iron - GGG50 |
Ball | stainless steel |
seat | PTFE |
Characterizing disc | stainless steel |
Packing | 2 EPDM O-rings, lubricated |
Electronic Pressure Independent Valves (ePIV)
Applications
Water-side control of heating and cooling systems for AHUs and heat pumps. Equal Percentage: Heating / cooling applications. Linear Characteristic: Bypass control.
Mode of Operation
The Electronic Pressure Independent Control Valve is a two-way valve which is unaffected by pressure variations in a system.
Product Features
Constant flow regardless of pressure variations in the system. Maximizes chiller ?T, preventing energizing additional chillers due to low ?-T. Simplifi ed valve sizing and selection, no Cv calculations required.
1. | Pressure independent valves compensate for pressure variations, performing a continual balancing function to maintain system performance at varying loads. |
2. | Precise flow control eliminates over-pumping and provides favorable energy savings. |
3. | Equal percentage flow characteristics leads to system controllability. |
4. | Pressure independent valve prevent energizing additional chillers by maintaining desirable Delta T. |
5. | Constant flow performance significantly reduces actuator movement, providing less hunting and wear on the valve assembly. |
6. | Pressure independent valves are selected based on coil flow rate and no Cv calculations are needed. |
Item Number:
P6300S-141+AKRX24-PI
Manufacturer:
Belimo
Manufacturer Part No:
P6300S-141+AKRX24-PI